communications, routing and pre-amplification of digital alarm tones and
voice (digital and analog) messages. The system shall be zoned for
messages (Custom and prerecorded) and tones as indicated on the drawings.
The following electronic tones shall be available from the amplifier: Slow
Whoop, High/Low, Horn, Chime, Beep, Stutter, Wail and Bell. The system
shall have a microphone and allow for general paging within the space.
Operation shall be either manually from a control switch or automatically
from the fire alarm control panel. Reset shall be accomplished by the fire
alarm control panel during panel reset.
2.7
FIRE DETECTION AND ALARM SYSTEM PERIPHERAL EQUIPMENT
2.7.1
Electromagnetic Door Hold-Open Devices
Devices shall be attached to the walls unless otherwise indicated. Devices
shall comply with the appropriate requirements of UL 228. Devices shall
operate on 24 Volt dc power. Compatible magnetic component shall be
and hold the doors open. When magnets are de-energized, they shall release
the doors. Magnets shall have a holding force of 111.2 N 25 pounds.
Devices shall be UL or FM approved. Housing for devices shall be brushed
aluminum or stainless steel. Operation shall be fail safe with no moving
parts. Electromagnetic door hold-open devices shall not be required to be
held open during building power failure.
2.7.2
Conduit
Conduit and fittings shall comply with NFPA 70, UL 6, UL 1242, and UL 797.
2.7.3
Wiring
**************************************************************************
NOTE: Do not penetrate SCIF perimeters with copper
signal line circuits. SCIF penetrations should be
either fiber optic cable or IDC. IDC circuits
penetrating the SCIF shall be filtered.
**************************************************************************
Wiring shall conform to NFPA 70. Wiring for 120 Vac power shall be No. 12
AWG minimum. The SLC wiring shall be [fiber optic] [or] [copper] cable in
accordance with the manufacturers requirements. Wiring for fire alarm dc
circuits shall be No. [16] [14] AWG minimum. Voltages shall not be mixed
in any junction box, housing, or device, except those containing power
supplies and control relays. Wiring shall conform to NFPA 70. System
field wiring shall be solid copper and installed in metallic conduit or
electrical metallic tubing, except that rigid plastic conduit may be used
under slab-on-grade. Conductors shall be color coded. Conductors used for
the same functions shall be similarly color coded. Wiring code color shall
remain uniform throughout the circuit. Pigtail or T-tap connections to
initiating device circuits, supervisory alarm circuits, and notification
appliance circuits are prohibited. T-tapping using screw terminal blocks
is allowed for style 5 addressable systems.
2.7.4
Special Tools and Spare Parts
**************************************************************************
NOTE: Remove last sentence when not required.
**************************************************************************