inputs specified:
a.
Help: Used to produce a display for all commands available to the
operator. The help command, followed by a specific command shall
produce a short explanation of the purpose, use, and system
reaction to that command.
b.
Acknowledge Alarms: Used to acknowledge that the alarm message
has been observed by the operator.
c.
Place Zone in Access: Used to remotely disable all intrusion
alarm circuits emanating from a specific zone. The system shall
be structured so that tamper circuits cannot be disabled by the
console operator.
d.
Place Zone in Secure: Used to remotely activate all intrusion
alarm circuits emanating from a specific zone.
e.
System Test: Allows the operator to initiate a system wide
operational test.
f.
Zone Test: Allows the operator to initiate an operational test
for a specific zone.
g.
Print Reports:
Allows the operator to initiate printing of
reports.
h.
Change Operator:
Used for changing operators.
i.
Security Lighting Controls:
Allows the operator to remotely turn
on/off security lights.
j.
Display Graphics: Used to display any graphic displays
implemented in the system.
2.4.3
Site Specific Database Software
2.4.3.1
Database Definition Process
Software shall be provided to define and modify each point in the database
using operator commands. The definition shall include all physical
parameters and constraints associated with each sensor, commandable output,
zone, etc. Each database item shall be callable for display or printing,
including EEPROM, ROM and RAM resident data. The database shall be defined
and entered into the central station by the Contractor based upon input
from the Government.
2.4.3.2
System Access Control
The system shall provide a means to define system operator capability and
functions through multiple, password operated protected operator levels.
At least 3 operator levels shall be provided. System operators and
managers with appropriate password clearances shall be able to change
operator levels for all operators. Three successive attempts by an
operator to execute functions beyond their defined level during a 24-hour
period shall initiate a software tamper alarm. A minimum of 32 passwords
shall display the operator's name or initials in the console's first field.
The system shall print the operator's name or initials, action, date, and
SECTION 13721A