The Contractor shall provide color coordinated consoles and equipment
cabinets. Equipment cabinets shall have front and back plexiglass doors,
thermostatic controlled bottom-mounted fan, and metal fitted and louvered
tops. One locking cabinet approximately 1.8 m 6 feet high, 1 m 3 feet
wide, 0.5 to 1 m 18 to 36 inches deep with 3 adjustable shelves, and 4
storage racks for storage of disks, tapes, printouts, printer paper,
ribbons, manuals, and other documentation shall be provided.
2.2.23
A self contained UPS, suitable for installation and operation at the
central station, shall be provided. The UPS shall be sized to provide a
facility is without an emergency backup generator, the UPS shall provide
necessary battery backup power for 24 hours. Equipment connected to the
UPS shall not be affected by a power outage of a duration less than the
rated capacity of the UPS. UPS shall be complete with necessary power
supplies, transformers, batteries, and accessories and shall include visual
indication of normal power operation, UPS operation, abnormal operation and
visual and audible indication of low battery power. The UPS shall be as
specified in Section 16265A UNINTERRUPTIBLE POWER SUPPLY (UPS) SYSTEM ABOVE
15 kVa CAPACITY. The UPS condition shall be monitored by the ESS and
displayed at the Central Station through the use of outputs or data stream
from the UPS.
2.2.24
Fixed Map Display
**************************************************************************
NOTE: A map display should be used only if required
by regulation or user requirement.
**************************************************************************
A fixed map display shall be provided showing a layout
of the protected
facilities. Zones corresponding to those monitored by
the system shall be
highlighted on the display. Status of each zone shall
be displayed using
LED's as required within each designated zone. An LED
test switch shall be
provided on the map display.
2.2.25
Enrollment Center Equipment
**************************************************************************
NOTE: The designer will calculate if 50 percent is
adequate for future use. If it is not, the designer
will specify the correct percentage.
**************************************************************************
Enrollment stations shall be provided and located as shown to enroll
personnel into, and disenroll personnel from, the system database. The
enrollment equipment shall only be accessible to authorized entry control
enrollment personnel. The Contractor shall provide enough credential cards
for all personnel to be enrolled at the site plus an extra [50] [_____]
percent for future use. The enrollment equipment shall include subsystem
configuration controls and electronic diagnostic aids for subsystem setup
and troubleshooting with the central station. A printer shall be provided
for the enrollment station which meets the requirements of paragraph Report
Printer.
SECTION 13720A
Page 40