alarm on premises).
Program as 24-hour alarm zone.
f.
Complete system test activated at the keypad.
g.
Capability for opening and closing reports to remote monitoring
location.
h.
Adjustable entry and exit delay times.
i.
Integral battery charger.
j.
Rechargeable 6 ampere-hour minimum sealed lead-acid battery.
k.
Minimum of two relay outputs, fused.
l.
Siren/bell output, fused and supervised.
m.
Capability for a minimum of two multiple function keypads.
n.
Capability to shunt or bypass selected interior zones while arming
perimeter protection and remaining interior zones.
o.
Capability for a minimum of seven assignable pass codes, keypad
programmable from suppressed master code.
2.4.15
[Bell] [Siren]
**************************************************************************
NOTE: Choose one of the following options.
**************************************************************************
[a.
Bell: Provide UL listed 255 mm 10 inch bell rated for 6 to 12
volts DC and having a sound output of 84 dB minimum. Bell shall
conform to UL 464 and UL 609, as applicable. Provide bell in
steel enclosed, weather-resistant box having tamper switches on
front cover and on back of box.]
[b.
Siren: Provide 30 watt, 8 ohm speaker and siren driver rated for
6 to 12 volts DC and having two distinct sound outputs. Siren
shall produce a sound level output of 103 to 106 dB at 3050 mm 10
feet. Siren shall conform to UL 464 and UL 609, as applicable.
Provide siren in metal enclosed, weather-resistant box having
tamper switches on front cover and on back of box.]
2.4.16
Strobes
Provide for visual indication of alarm activation. Strobe shall flash
simultaneously with [siren] [bell] and shall be 75 candela minimum with
flash rate of 60 per minute. Strobe shall be designed to operate on 12
volts DC and shall conform to UL 1638.
2.4.17
Central Station Receiver/Printer
Provide a microprocessor based digital alarm receiver conforming to UL 1610
to receive and display information transmitted by alarm control
panels/communicators over the standard telephone network. Receiver shall
be capable of handling Ademco low or high speed, Sescoa, Radionics, and
BFSK formats with either three- or four-digit subscriber identification and
four plus two formats on the same line card. [Receiver shall also
SECTION 13702N
Page 28