occupied facilities being transferred or resolving
facility-related work due to an occupant child with
an elevated blood lead. In these projects, it is
required that the specification editor has
appropriate training regarding lead-based paint
activities. Certification as a project designer per
40 CFR 745 is required.
**************************************************************************
**************************************************************************
NOTE: Where LBP/PWL is not specifically being
removed/controlled as a hazard abatement action or
deleading, use Section 13282N LEAD IN CONSTRUCTION.
**************************************************************************
**************************************************************************
NOTE: The classification of the lead-based paint or
paint with lead as hazardous waste must be performed
in accordance with 40 CFR 261, and in the design
phase of the project. This classification is
prerequisite to the requirement of special handling,
storage, and disposal according to Federal, state
and local hazardous waste management regulations.
**************************************************************************
**************************************************************************
NOTE: When historic preservation work will remove
LBP/PWL, refer to the Secretary of the Interior's
Standards for the Treatment of Historic Properties
and/or Brief 37, "Appropriate Methods for Reducing
Lead-Paint Hazards in Historic Housing" as
appropriate.
**************************************************************************
**************************************************************************
NOTE: Projects involving housing improvement,
maintenance, or repair are not considered a
lead-based paint hazard abatement action even if the
effect of the work removes (or controls) lead
exposure potentials to the occupants. However,
appropriate precautions for protecting occupants and
leaving the housing clean (clearance) after
concluding any work disturbing paint with lead must
be considered. Specific training and certification
requirements (40 CFR 745 or authorized state program
requirements) may not be necessary for all projects.
However, it is strongly recommended that the
specification editor have appropriate training
regarding lead-based paint.
**************************************************************************
**************************************************************************
NOTE: Obtain from the activity information on
lead-based paint/paint with lead to be removed by
the project.
**************************************************************************
**************************************************************************
NOTE: Projects that involve cutting, sawing,
SECTION 13283N
Page 4