NOTE: Insert additional details describing the
specific project for which this specification is
being used. Projects involving military
incorporate the applicable requirements of
MIL-STD-188-124, "Grounding, Bonding and Shielding
for Common Long Haul/Tactical Communication
Systems." Be aware that standard manufactured
shielded doors are not designed for exposure to
weather.
**************************************************************************
Section 16050N BASIC ELECTRICAL MATERIALS AND METHODS, applies to this
section, with the additions and modifications specified herein. The
enclosure[s] shall be capable of being erected, disassembled, and reerected
entirely from its interior without special tools [, except where RF
enclosure ceiling is specified as being supported by the structural ceiling
above]. Provide enclosure[s] complete with [power line filters,]
[telephone/signal line filters,] [RF air vents,] [penetrations for
compressed air lines, water lines and _____,] [coaxial cables,] [lighting
fixtures,] [workbenches with convenience outlets,] and door assembly.
Provide each item with fittings and hardware necessary for a complete and
operable RF shielded enclosure. Where two or more units of the same type,
class, and size of equipment are required, these units shall be products of
a single manufacturer. Provide means of completely isolating the structure
electrically from the building in which it is to be installed.
1.2.1
Mechanical Work
**************************************************************************
NOTE: Modify or delete these paragraphs as required
for each project. Additional items such as raised
computer floors may be specified in the same manner.
**************************************************************************
**************************************************************************
NOTE: Insert appropriate Section number and title
in blank below using format per UFC 1-300-02.
**************************************************************************
Provide complete shielded enclosure[s] including work specified in [_____]
[and [_____]].
1.2.2
Electrical Work
**************************************************************************
NOTE: Modify or delete these paragraphs as required
for each project. Additional items such as raised
computer floors may be specified in the same manner.
**************************************************************************
**************************************************************************
NOTE: Insert appropriate Section number and title
in blank below using format per UFC 1-300-02.
**************************************************************************
Conform to the requirements of the NFPA 70, National Electrical Code.
Provide a complete shielded enclosure[s] including work specified in
[_____] [and [_____]].