Designer will locate thermometer on the plans,
mounted outside the refrigerator, in a location that
will preclude vibration, will not interfere with the
operation of the door, will provide protection from
damage, and will allow easy reading. The sensor
part will be located to measure the air temperature
in the warmest part of the refrigerator. The
thermometer will not be located on the door panel.
**************************************************************************
Refrigerators shall be prefabricated, commercial, walk-in type suitable for
the intended use. Mercury shall not be used in thermometers. Units shall
conform to UL 207, UL 471, and NSF 7 [floorless,] [floor panel] design type
and size as indicated, and the following:
2.9.1
Miscellaneous Requirements
2.9.1.1
Closure Panels
Closure panels and/or trim strips to the building walls and ceiling shall
be installed with concealed attachments. Closure/trim shall be of the same
material as the wall panels unless otherwise noted.
2.9.1.2
I-Beam Supports
Wherever compartment dimension exceeds the clear-span ability of ceiling
panels, I-beam supports shall be provided on the exterior of the ceiling or
supported by spline-hangers. Thirteen mm Half inch diameter steel rods
shall be installed through beam/hangers and secured to the structure above.
Beams or posts within compartments will not be acceptable.
2.9.1.3
Identification Signs
Engraved phenolic plastic compartment identification signs 300 by 50 mm 12
by 2 inches high in selected color with 25 mm 1 inch high letters shall be
mounted on door above view window.
2.9.1.4
Door
Door panels inner and outer skins shall be of 1 mm 0.040 inches patterned
aluminum. Doors shall be filled with insulation [100] [_____] mm [4]
[_____] inches thick, and [one] [two] per [unit] [section]. Hardware shall
be stainless steel.
2.9.1.5
Strip Curtains
Transparent flexible vinyl reinforced strip curtains shall be provided
which are anchored at top and able to be replaced individually. Strips
shall be a minimum of 200 mm 8 inches in width and 2 mm 0.08 inches thick.
2.9.1.6
Door Stops
Door stops shall be provided, where necessary, to prevent walk-in
refrigerator doors from striking adjacent walls, plumbing fixtures or food
service equipment when door is open.
2.9.1.7
Protective Bumpers
[The exterior side of refrigerator that are not installed against each