Maximum temperature rise across heater
[20] [_____] degrees C
[35] [_____] degrees F
Catalyst chamber empty bed contact time
[1.0] [_____] seconds
Max. ozone concentr. into destruct unit
[1.0] [_____] percent by
weight
Off gas flow rate (maximum)
[_____] cubic m/s
[_____] scfm
Maximum catalyst bed temperature
[120] [_____] degrees C
[250] [_____] degrees F
Off gas temperature to catalyst bed
[15] [_____] degrees C
[60] [_____] degrees F
[480] [_____] volts,
[3] [_____] phase, 60
hertz.
The catalyst shall be non-hazardous [manganese dioxide/copper oxide]
[nickel] [_____] based material suitable for catalytic ozone destruction at
the specified conditions. The catalyst containment unit shall be provided
with a flanged and bolted top or hatch a minimum of 300 mm 12 inch in
diameter to facilitate change out of the catalyst material when the
catalyst is exhausted.
2.2.6
Hydrogen Peroxide System
**************************************************************************
NOTE: Edit Section 11242A CHEMICAL FEED SYSTEMS to
provide on-off, set point, or proportional control
as appropriate.
Hydrogen peroxide storage system requirements should
be coordinated with suppliers to ensure material
compatibility. Floating roof manway area should
equal 1 in 2 per 400 L (100 gallons) for solutions
less than 52 percent, and 2 in 2 per 400 L (100
gallons) for solutions greater than 52 percent.
Process safety management requirements must be
followed any time more than 3375 kg (7500 pounds) of
H2O2 is stored, or the solution strength is greater
than 52 percent; refer to 29 CFR 1910.119 for
information.
Hydrogen peroxide storage tanks should be located
outside when possible. Polyethylene should not be
used for peroxide concentrations greater than 52
percent.
**************************************************************************
The hydrogen peroxide storage tank shall be constructed of cross linked
polyethylene, 316 stainless steel, or 99.5 percent pure aluminum alloys
designated in [ASTM B 209M] [ASTM B 209] as 1060, 5254, 5652. Hydrogen
peroxide storage tanks shall be provided with secondary containment [as
detailed on the drawings] [_____] with a minimum capacity equal to [110]