where necessary to achieve this performance. A stilling baffle shall be
provided in the aeration tank before the outlet into the settling tank.
2.7.3
Settling Tank
**************************************************************************
NOTE: Delete the first and fourth sentences for
extended aeration type plants above 4.38 L/s 100,000
GPD capacity, step aeration type plants above 3.0 L/s
67,500 GPD capacity, and for all complete mixing
type plants.
**************************************************************************
**************************************************************************
NOTE: Delete reference to mechanical sludge
collection equipment for extended aeration type below
0.66 L/s 15,000 GPD capacity. For plants below
0.66 L/s 15,000 GPD capacity, hopper bottom only
should be specified for settling tanks. For plants
above 4.38 L/s 100,000 GPD capacity, mechanical
sludge collectors only should be used in settling
tanks. For plants between 0.66 L/s and 4.38 L/s
15,000 and 100,000 GPD capacity, either hopper
bottom or mechanical sludge collector should be
allowed as a Contractor's option. However, of the
various types of mechanical sludge collectors,
rotating sludge collectors appear to be available
for plants of 1.31 L/s 30,000 GPD and above;
chain-and-flight, 1.75 L/s 40,000 GPD and above;
and above.
**************************************************************************
**************************************************************************
NOTE: Settling tanks shall have a freeboard of not
less than 300 mm one foot for plants of 0.88 L/s
20,000 GPD capacity and below, and not less than 450
mm one foot 6 inches for plants of more than 0.88 L/s
20,000 GPDcapacity.
**************************************************************************
**************************************************************************
NOTE: In all plants (except circular plants with
concretric inner settling tank) where the design
flow exceeds 4.38 L/s 100,000 GPD, the settling tank
should be in multiple units each capable of
independent operation and whose combined capacity
equals the design flow rate. In fourth sentence,
delete first and third optional wordings when design
flow is 4.38 L/s 100,000 GPD and below; delete
second optional wording when design flow exceeds
4.38 L/s 100,000 GPD.
**************************************************************************
**************************************************************************
NOTE: Delete the first and fourth sentences for
extended aeration type plants above 4.38 L/s 100,000
GPD capacity, step aeration type plants above 3.0 L/s
67,500 GPD capacity, and for all complete mixing