steel or concrete (except that all-steel would be
needed for relocatable plants).
**************************************************************************
**************************************************************************
NOTE: The applicable requirements for cast-in-place
concrete as specified in Section 03300N
CAST-IN-PLACE CONCRETE and Section 03410N PLANT
PRECAST STRUCTURAL CONCRETE should be incorporated
into the appropriate section of the project
specification.
**************************************************************************
**************************************************************************
NOTE: Insert appropriate Section numberS and titleS
in blankS below using format per UFC 1-300-02.
**************************************************************************
Concrete work includes [concrete plant walls, partitions, and bottom;]
[support slab for all-steel plant or concrete bottom for steel wall plant;]
and concrete pad for equipment support. Cast-in-place concrete shall be in
accordance with [_____] and [_____]. Precast concrete shall be in
accordance with [_____] and [_____]. Results of Government-made soil
bearing tests will be furnished to the Contractor.
2.5
LUBRICATION
All moving parts of equipment requiring lubrication shall have means
provided for such lubrication and shall be lubricated prior to delivery.
2.6
MATERIALS AND EQUIPMENT
2.6.1
General
**************************************************************************
NOTE: Delete reference to mechanical aerator when
step aeration type or complete mixing type is
specified, or when not allowed for extended aeration
type. Mechanical aerator may not be suitable for
use in areas having prolonged periods of
sub-freezing temperatures when spray may form
accumulation of ice. Consideration should be given
to temperature and detention time of the liquid and
freeboard in the tank in determining temperatures
that may be tolerated. Mechanical aerator is not
suitable for extended aeration type where eventual
conversion to step aeration is contemplated.
**************************************************************************
**************************************************************************
NOTE: Delete reference to mechanical sludge
collection equipment for extended aeration type below
0.66 L/s 15,000 GPD capacity. For plants below
0.66 L/s 15,000 GPD capacity, hopper bottom only
should be specified for settling tanks. For plants
above 4.38 L/s 100,000 GPD capacity, mechanical
sludge collectors only should be used in settling
tanks. For plants between 0.66 L/s and 4.38 L/s
15,000 and 100,000 GPD capacity, either hopper
SECTION 11375N
Page 25