b.
[Model Number, Control Number, or equivalent]
c.
Date of manufacture by week, month or quarter and year. This may
be abbreviated or be in a traceable code such as the lot number.
d.
Correct mounting position including threat side and secure side
(by removable label on glazing material).
e.
Code indicating bullet-resistant rating and test standard used (by
removable label on glazing material).
2.14
FASTENERS
Fasteners exposed to view shall match in color and finish and shall
harmonize with the material to which fasteners are applied. Fasteners
shall be in accordance with Section 05500A MISCELLANEOUS METAL.
2.15
CORROSION PROTECTION - DISSIMILAR MATERIALS
Contact surfaces between dissimilar metals and aluminum surfaces in contact
with concrete, masonry, pressure-treated wood or absorptive materials
subject to wetting, shall be given a protective coating in accordance with
Section 09900 PAINTS AND COATINGS.
2.16
SHOP/FACTORY FINISHING
All factory or manufactured components shall be shop finished as indicated
below.
2.16.1
Ferrous Metal
Surfaces of ferrous metal, except galvanized and stainless steel surfaces,
shall be cleaned and shop coated with the manufacturer's standard
protective coating other than a bituminous protective coating, compatible
with finish coats. Prior to shop painting, surfaces shall be cleaned with
solvents to remove grease and oil, and with power wire-brushing or
sandblasting to remove loose rust, loose mill scale and other foreign
substances. Surfaces of items to be embedded in concrete shall not be shop
painted.
2.16.2
Galvanizing
Items specified to be galvanized shall be hot-dip processed after
fabrication. Galvanizing shall be in accordance with ASTM A 123/A 123M or
ASTM A 653/A 653M as applicable.
2.16.3
Aluminum
Unless otherwise specified, aluminum items shall be standard mill finish.
Anodic coatings shall conform to paragraph FINISHES.
PART 3
EXECUTION
3.1
EXAMINATION
Existing work shall be examined to ensure that it is ready for installation
or erection of the components. Components shall be checked and corrected
for racking, twisting, and other malformation prior to installation.
SECTION 11035
Page 29