2.3
WALL BASE
2.3.1
Resilient Base
Base shall be [Type I (rubber)] [or] [Type II (vinyl)] Style B, (coved).
Base shall be [100] [150] mm [4] [6] inch high and a minimum 3 mm 1/8 inch
thick. [Preformed outside] [Job formed] corners shall be furnished.
2.3.2
Self-Coving
**************************************************************************
NOTE: Self-coving will be used when highest
standard of cleanliness is required.
**************************************************************************
Self-coving shall consist of conductive floor tile over a cove stick and
shall have [cove cap] [and optional metal corners] as recommended by the
manufacturer of the tile.
2.4
ACCESSORIES
Accessories shall be as recommended by the manufacturer of the flooring.
2.5
ELECTRICAL GROUND CONNECTION
**************************************************************************
NOTE: The conductive vinyl tile is installed in a
conductive adhesive. The floor system is grounded
to an external ground by a short grounding strip,
usually on a room-by-room basis. Designer must
provide for connection to an external ground and
should coordinate with conductive tile manufacturers
during design stage regarding connections to
external ground. Designer will show ground
connection to the external ground on the drawings.
**************************************************************************
Connection between the conductive floor system and the external grounding
system shall be provided. Contact with the conductive floor system shall
be with conductive grounding strip and shall have the greater of the
following: a minimum contact area of 5806 square mm (9 square inch) 9
square inch or the dimensions recommended by the manufacturer. The
grounding conductor shall be as recommended by the manufacturer of the
flooring.
2.6
COLOR
Color shall be [in accordance with Section 09915 COLOR SCHEDULE] [_____].
PART 3
EXECUTION
3.1
SURFACE CONDITIONS
**************************************************************************
NOTE: Curing and sealing compounds should not be
used on concrete surfaces to receive conductive
vinyl tile. If a curing compound is required, it
must be coordinated for compatibility with the
flooring adhesive.
SECTION 09660
Page 6