c.
Use sealant and tape glazing, with glazing sealant full height
against removable exterior stops with heel bead or glazing sealant
and glazing tape full height against fixed interior stops for
[_____].
d.
Use sealant and tape glazing, with glazing sealant cap beads above
glazing tape against both exterior and interior stops for [_____].
Removable stops may be on either exterior or interior side of
glass.
e.
Use tape, sealant, and compound glazing, with glazing tape full
height against fixed exterior stops, glazing compound as a cap
bead above heel bead sealant and against removable interior stops
for [_____].
f.
Use tape, sealant, and gasket glazing, with glazing tape full
height against fixed exterior stops, glazing sealant as a heel
bead at edge of glass, and preformed vision strip gasket against
removable interior snap-on stops for [_____].
g.
Use compression gasket glazing, with compression gaskets both
sides of glass and adjustable or snap-on interior stops for
[_____].
h.
Use lock-strip gasket glazing, with lock-strip glazing gaskets for
[_____]. Install gaskets in accordance with manufacturer's
instructions using special tools and lubricants. When lock-strip
type gaskets are used for glazing insulating glass units, follow
glass manufacturer's recommendations regarding horizontal wall
supports between vertical units, setting blocks, weep holes, and
the use of supplementary wet sealants.
3.2.6.5
Void Space
Heat absorbing, insulating, spandrel, and tempered glass, and glass of
other types that exceed 2540 united millimeters 100 united inchesin size:
Provide void space at head and jamb to allow glass to expand or move
without exuding the sealant.
3.2.6.6
Insulating Glass
Provide adequate means to weep incidental water and condensation away from
the sealed edges of insulated glass units and out of the wall system. The
weeping of lock-strip gaskets should be in accordance with the
recommendation of the glass manufacturer.
3.2.6.7
Insulating Glass With Edge Bands
Insulating glass with flared metal edge bands set in lock-strip type
gaskets: Follow glass manufacturer's recommendations and add supplementary
wet seal as required; when used with glazing tape, use tapered tape.
3.2.7
Firestopping
Provide firestopping [, where indicated,] in openings between wall system
and floor at each story to prevent passage of flame and hot gases from
floor to floor under extended fire exposure. Installed fire stopping shall
remain in place under extended fire exposure despite distortions that may
occur in wall system components. Securely attach anchoring or containment
SECTION 08900