2.10.4
Groupings
Conductors shall be grouped by systems and tied with nylon tie straps.
Shape wire bundles for support from top and sides of structure. Do not
attach support devices to removable panels.
2.10.5
Protection
Where groups of conductors or single conductor pass through metal framing
or panels, protect conductors with rubber or plastic grommets.
PART 3
EXECUTION
3.1
INSTALLATION
3.1.1
Locking Control Panels
Graphic locking control panels and linear locking control panels shall be
installed in metal control cabinets as specified. Coordinate installation
of locking control panels in metal control cabinets with respect to
dimensions, mounting and accessibility.
3.1.2
Security Equipment Cabinets
in the security equipment or electrical room closest to the associated
locking control panel.
3.1.3
Junction Boxes
Provide junction boxes required for locking systems wiring in accordance
with Section 16402 INTERIOR DISTRIBUTION SYSTEM. Do not install junction
boxes and pull boxes in areas accessible to prisoners.
3.1.4
Conduit Systems
Provide conduit systems required for locking systems wiring in accordance
with Section 16402 INTERIOR DISTRIBUTION SYSTEM.
3.1.5
Wiring Systems
3.1.5.1
Wiring Specification
The work under this section includes the installation of wiring for the
electrically operated locks, gates, and doors. The actual connections to
individual locks, doors, and gates and the actual connections in the
control panels and consoles shall be done under this section. Coordinate
this portion of the work with the detention hardware manufacturer.
3.1.5.2
Grouping
Conductors within junction boxes, pull boxes, and equipment enclosures
shall be grouped and laced with nylon tie straps with identification tabs,
in individual sets servicing individual lock sets or operating mechanisms.
Conductor groups shall be identified on the strap with respect to room or
operator served.