brass plate with 13 mm 1/2 inch high raised letters. Label shall be
permanently attached to the door and shall not be painted.
2.7.1
Contractor's Option
In lieu of UL or FM P7825 labels, the fire doors may bear the label of a
nationally recognized testing agency. The testing agency shall be
adequately equipped and competent to perform services equivalent to the UL
indicating compliance with required ratings shall accompany the
certificates of compliance.
2.7.2
Oversized Doors
Where fire doors and frames exceed the size for which testing and labeling
service is offered, furnish certificates of inspection from the testing
laboratory. The certificate shall state that the doors, frames, and
hardware to be provided are identical in design, materials, and
construction to a door that has been tested and rated.
PART 3
EXECUTION
3.1
INSTALLATION
Install fire doors in accordance with NFPA 80 and the manufacturer's
approved instructions and shop drawings. Doors shall be free from warp,
twist, or distortion and shall be lubricated and properly adjusted to
operate freely.
-- End of Section --
SECTION 08162
Page 12