Synthetic rubber washers shall be used between the anchor connector plates
and the moisture barrier. A clutch torque slip screw gun shall be used on
screws attaching veneer anchors to cold-formed steel members. Veneer
anchors with corrugated sheet metal or wire mesh members extending across
the wall cavity shall not be used. There shall be one veneer anchor for
each 0.2 square meters two square feet of wall and shall be attached to
steel studs and other supports with a maximum spacing of 600 mm 24 inches
on center. For pintle-eye anchors the vertical distance between the pintle
section horizontal wires and the eye section horizontal wires shall not
exceed 13 mm 1/2 inch. Dovetail slots shall be installed as specified in
the Section [03300A CAST-IN-PLACE STRUCTURAL CONCRETE][03300N CAST-IN-PLACE
CONCRETE].
3.9
FLASHING
**************************************************************************
NOTE: Base, head and sill flashing details should
be shown on wall section on the drawings. To be
most effective, the flashing should extend through
the exterior face of the masonry veneer and turn
down to form a drip. If flashing is to extend
through the veneer, the last sentence of the
paragraph should be retained and the appropriate
portions of Section 07600 FLASHING AND SHEET METAL
shall be changed to reflect this type of flashing
installation. If, for esthetic reasons, it is
necessary to conceal the flashing, the last sentence
of the paragraph will be deleted.
**************************************************************************
Continuous flashing shall be provided at the bottom of the wall cavity just
above grade. Flashing shall also be provided above and below openings at
lintels and sills, at shelf angles, and as indicated on the drawings.
Flashing shall be as detailed and as specified in Section 07600 FLASHING
AND SHEET METAL. Flashing shall be lapped a minimum of 150 mm 6 inches at
joints and shall be sealed with a mastic as recommended by the flashing
manufacturer. Ends over doors, windows and openings shall be turned up and
secured. Flashing shall be lapped under the moisture barrier a minimum of
150 mm 6 inches and securely attached to the gypsum sheathing. Flashing
shall extend through the exterior face of the masonry veneer and shall be
turned down to form a drip.
3.10
MASONRY VENEER
**************************************************************************
NOTE: The wall cavity air space should be a minimum
of 50 mm (2) and a maximum of 100 mm (4 inches)
wide. Coordinate cavity dimensions with standard
lintel and shelf angle dimensions.
Bond pattern should be running bond unless there are
compelling architectural reasons to select another
pattern.
**************************************************************************
Exterior masonry wythes shall be constructed to the thickness indicated on
the drawings. A cavity consisting of a [50] [_____] mm [2] [_____] inch
minimum width air space will be provided between the moisture barrier and
the masonry veneer. Masonry veneer shall not be installed until the
SECTION 04810
Page 22