Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are [for Contractor Quality Control
approval.][for information only. When used, a designation following the
"G" designation identifies the office that will review the submittal for
the Government.] The following shall be submitted in accordance with
Section 01330 SUBMITTAL PROCEDURES:
SD-03 Product Data
Splicing Waterstops[; G][; G, [_____]]
Procedures for splicing waterstops shall be submitted for
approval.
SD-04 Samples
Field Molded Sealants and Primer
Four L One gallon of field-molded sealant and 1 L one quart of
primer (when primer is recommended by the sealant manufacturer)
shall be provided for testing.
Waterstops[; G][; G, [_____]]
Waterstop materials and splice samples shall be submitted for
inspection and testing and shall be identified to indicate
manufacturer, type of material, size and quantity of material and
shipment represented. Each materials sample shall be a piece not
less than 300 mm 12 inches long cut from each 60 m 200 feet of
finished waterstop furnished, but not less than a total of 1.2
linear meters 4 linear feet of each type and size furnished. For
spliced segments of waterstops to be installed in the work, one
spliced sample of each size and type for every 50 splices made in
the factory and every 10 splices made at the job site shall be
furnished for inspection and testing. The spliced samples shall
be made using straight run pieces with the splice located at the
mid-length of the sample and finished as required for the
installed waterstop. The total length of each spliced sample
shall be not less than 300 mm 12 inches long.
SD-06 Test Reports
Premolded Expansion Joint Filler Strips
Compression Seals and Lubricant
Metallic Waterstops
Certified manufacturer's test reports shall be provided for
premolded expansion joint filler strips, compression seals and
lubricant, and metallic waterstops to verify compliance with
applicable specification.
SECTION 03151A