Use Section 16402 INTERIOR DISTRIBUTION SYSTEM, for
empty conduit CATV systems instead of this section.
Include the backboard, outlet, faceplate, and other
special requirements in that section.
**************************************************************************
**************************************************************************
NOTE: As a minimum, the Designer shall provide the
CATV system loss and tilt compensation calculations
using manufacturer's data and including the
amplifier sizes and system requirements to the
EFA/EFD. Project drawings shall show the cable
system, grounding, homeruns, and passive and active
devices in a one-line diagram. Where television
mounting brackets are required on a job, provide
bracket requirements and details in architectural
drawings and specifications.
**************************************************************************
PART 1
GENERAL
1.1
REFERENCES
**************************************************************************
NOTE: Issue (date) of references included in
provided by the latest guide specification. Use of
SpecsIntact automated reference checking is
recommended for projects based on older guide
specifications.
**************************************************************************
The publications listed below form a part of this specification to the
extent referenced. The publications are referred to within the text by the
basic designation only.
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE C2
(2002) National Electrical Safety Code
IEEE C62.41
(1991; R 1995) Recommended Practice for
Surge Voltages in Low-Voltage AC Power
Circuits
NATIONAL CABLE AND TELECOMMUNICATIONS ASSOCIATION (NCTA)
NCTA RP
(2003) NCTA Recommended Practices for
Measurements on Cable Television Systems
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70
(2005) National Electrical Code
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
47 CFR 76.605
Technical Standards
SECTION 16783N
Page 4