cnetered at 500 and 4000 Hz. Use sound level meter with octave band
filters to measure level at three locations in each paging zone. Maximum
permissable variation in level is plus or minus 3 dB; in levels between
adjacent zones, plus or minus 5 dB.
Power output Test: Measure electrical power output of each paging
amplifier at normal gain setting of 150, 1000 and 2500 Hz. Maximum
variation in power output at these frequencies is plus or minus 3 dB.
3.4
TRAINING
The Contractor shall conduct a training course for [_____] members of the
operating staff and for [______] members of the maintenance staff as
designated by the Contracting Officer. The training course will be given
at the installation during normal working hours for a total of [_____]
hours for the operating staff and [______] hours for the maintenance staff,
and shall start after the system is functionally complete but prior to
final acceptance tests. The field instructions shall cover all of the
items contained in the approved operating and maintenance instructions, as
well as the demonstration of routine maintenance operations. The
Contracting Officer shall be notified at least 14 days prior to the start
of the training course.
3.5
INTERCOMMUNICATION SYSTEM, DATA PACKAGE 3
The Contractor shall submit data package in accordance with Section 01781
OPERATION AND MAINTENANCE DATA.
-- End of Section --