NOTE: ANSI C37.06 lists standard ratings. A
short-circuit study is required to specify ratings.
**************************************************************************
be of the outdoor three-pole type, with single or multiple tanks and
frame-mounted or floor-mounted on a common base in accordance with the
manufacturer's standard design. Control voltage shall be [48] [125] volts
dc. Ratings shall be as follows:
Nominal voltage...............................[_____]
Rated maximum voltage.........................[_____]
Maximum symmetrical interrupting capacity.....[_____]
Maximum asymmetrical interrupting capacity....[_____]
3-second short time current carrying capacity.[_____]
Close and latch capacity......................[_____]
Rated continuous current......................[_____]
Maximum interrupting time.....................[_____]
Permissible tripping delay....................[_____]
Reclosing time (adjustment range).............[_____]
Duty cycle at rated conditions................[_____]
Basic Insulation Level (BIL)..................[_____]
2.11.1
**************************************************************************
NOTE: Delete items "e" and "f" if not required.
**************************************************************************
of the serving utility, and of the protected transformer, and shall include
the following control and monitoring system items that shall be mounted in
the instrument and relay cabinet.
a.
b.
A circuit breaker control switch for local and remote control
operation.
c.
Three overcurrent relays, devices 50/51.
d.
One residually-connected ground-overcurrent relay, device 50/51N.
e.
Three directional overcurrent relays, device 67.
f.
One ground-directional-overcurrent relay, device 67N.
g.
Three transformer differential relays, device 87T and an auxiliary
SECTION 16475A
Page 21