run elsewhere will comply with communication
agency's policy.
**************************************************************************
[Ducts shall be single, round-bore type, with wall thickness and fittings
suitable for the application.] [Duct lines shall be concrete-encased,
thin-wall type.] [Duct lines shall be nonencased direct-burial, thick-wall
type.][Duct lines shall be concrete-encased, thin-wall type for duct lines
between manholes and for other medium-voltage lines.][[Low-voltage lines]
[or] [Communication lines] run elsewhere may be direct-burial, thick-wall
type.][Where concrete encasement is not required, low-voltage circuits may
utilize factory-installed cable in coilable plastic duct.]
2.6.1
Metallic Conduit
Intermediate metal conduit shall comply with UL 1242. Rigid galvanized
steel conduit shall comply with UL 6 and ANSI C80.1. Metallic conduit
fittings and outlets shall comply with UL 514A and NEMA FB 1.
2.6.2
Nonmetallic Ducts
**************************************************************************
NOTE: Bituminized fiber duct should be specified
only for connection to existing bituminized fiber
duct systems. Delete the paragraph if not required.
Specify thin-wall or schedule 40 plastic duct for
concrete encasement and thick-wall or schedule 40 or
schedule 80 plastic duct for direct-burial and riser
applications (riser bends should be metallic conduit
where cables are to be pulled into ductline).
**************************************************************************
2.6.2.1
Bituminized Fiber Duct
UL 1684 for [Type I (Thinwall)][Type II (Thickwall)].
2.6.2.2
Concrete Encased Ducts
UL 651 Schedule 40 or NEMA TC 6 & 8 Type EB.
2.6.2.3
Direct Burial
UL 651 [Schedule 40][and][Schedule 80][as indicated], or NEMA TC 6 & 8 Type
DB.
2.6.3
Conduit Sealing Compound
Compounds for sealing ducts and conduit shall have a putty-like consistency
workable with the hands at temperatures as low as 2 degrees C 35 degrees F,
shall neither slump at a temperature of 150 degrees C 300 degrees F, nor
harden materially when exposed to the air. Compounds shall adhere to clean
surfaces of fiber or plastic ducts; metallic conduits or conduit coatings;
concrete, masonry, or lead; any cable sheaths, jackets, covers, or
without dissolving, noticeably changing characteristics, or removing any of
the ingredients. Compounds shall have no injurious effect upon the hands
of workmen or upon materials.