--Section L-16303N UNDERGROUND ELECTRICAL WORK
**************************************************************************
**************************************************************************
NOTE: The following information shall be indicated
1. Site Plan showing location, space available, and
desired arrangement of switchgear.
2. Single-line diagram showing: nominal system
voltage; number and configuration of switched ways;
type, number, and size of conductors for each
circuit; and method of power cable termination (200
ampere loadbreak connectors, or 600 ampere deadbreak
connectors). Individually identify each switched way
as load or fault interrupter and single-pole or
three-pole tripping.
3. Grounding Detail with ground rods, ground loop
and interconnecting cables when interconnecting with
other grounding systems or if multiple switches are
provided.
4. Special conditions, such as altitude,
temperature and humidity, exposure to fumes, vapors,
dust, and gases.
**************************************************************************
PART 1
GENERAL
1.1
REFERENCES
**************************************************************************
NOTE: Issue (date) of references included in
provided by the latest guide specification. Use of
SpecsIntact automated reference checking is
recommended for projects based on older guide
specifications.
**************************************************************************
The publications listed below form a part of this specification to the
extent referenced. The publications are referred to within the text by the
basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI C57.12.29
(1999) Pad-Mounted Equipment - Enclosure
Integrity for Coastal Environments
ASTM INTERNATIONAL (ASTM)
ASTM A 167
(2004) Stainless and Heat-Resisting
Strip
ASTM D 1535
(2001) Specifying Color by the Munsell
System
SECTION 16341N
Page 4