handle mechanism. The cross sectional area of the braid shall be
equivalent to a No. 4 AWG conductor, minimum.
2.6
SUBSTATION EQUIPMENT
**************************************************************************
NOTE: Make selections in this paragraph and in
paragraph STATION ARRANGEMENT as appropriate for the
installation. For this specification an articulated
primary unit substation has both high-voltage and
low-voltage sections mechanically coupled to the
transformer. A primary unit substation has only the
low-voltage section mechanically coupled to the
paragraph Primary Unit Substation or Substation
Transformer or Articulate Primary Unit Substation
will apply. For voltages through 34.5 kV, the
primary switch/breaker should be
mechanically-coupled or bus-duct-connected to the
aerial-bus-connected to the transformer primary. In
general, the transformer secondary should be
mechanically-coupled or bus-duct-connected to the
secondary switchgear through and including 34.5 kV.
**************************************************************************
The installation shall be [of the switching station] [of the primary unit
substation] [of the substation transformer] [an articulated primary unit
substation of the [radial] [distributed-network] [spot-network]
[secondary-selective] [duplex]] type. [The initial capacity of the
substation is based on the [55/65 degrees C] [self-cooled] [single-stage
cooled] [two-stage cooled] [transformer capacity shown]]. The number of
outgoing [lines] [distribution feeders] shall be as shown. Outgoing
circuits shall be three-phase [three-wire] [four-wire] type [with [a bare]
[an insulated] neutral] having a voltage rating of [_____] kV
phase-to-phase. The insulated neutral shall have insulation rated not less
than 1000 volts. Outgoing circuit equipment shall be rated for a nominal
voltage class of [_____] kV and shall have a BIL of not less than [_____]
kV. Outgoing circuits shall leave the station [aerially] [underground] [in
cable trays].
2.6.1
**************************************************************************
NOTE: Coordinate with paragraph Specific Unit
Requirements.
Since some POWER TRANSFORMER manufacturers prefer
the use of forced-oil-cooling over
forced-air-cooling for the second stage, allow
either option. Specify an oil preservation system
for self-cooled capacities greater than 5000 kVA.
Coordinate load-tap-changing type with Voltage
Regulator section of paragraph AUXILIARY SUBSTATION
EQUIPMENT.
**************************************************************************
SECTION 16311A
Page 33