Free Discharge Motors
Unit Capacity (L/S)
Maximum Power Consumption (Watts)
115V
230V
277V
94
70
110
90
142
100
110
110
189
170
150
150
283
180
210
220
378
240
240
230
472
310
250
270
566
440
400
440
Free Discharge Motors
Unit Capacity (cfm)
Maximum Power Consumption (Watts)
115V
230V
277V
200
70
110
90
300
100
110
110
400
170
150
150
600
180
210
220
800
240
240
230
1000
310
250
270
1200
440
400
440
High Static Motors
Unit Capacity (L/S)
Maximum Power Consumption (Watts)
94
145
142
145
189
210
283
320
378
320
472
530
566
530
High Static Motors
Unit Capacity (cfm)
Maximum Power Consumption (Watts)
200
145
300
145
400
210
600
320
800
320
1000
530
1200
530
2.9.2
Base unit shall include air plenums, air-discharge nozzles, air discharge
grilles, recirculation grilles, water coil assembly, valve and piping
package, condensate drain pan, and adjustable air-balancing dampers, plus
an enclosure for cabinet models and casing for concealed models. Each unit
shall produce not less than the capacity indicated without exceeding the
indicated static pressure. The sound power level shall be as indicated.
Sound power level data or values for these units shall be based on tests
conducted according to ANSI S12.51. Sound power values apply to units
provided with factory fabricated cabinet enclosures and standard grilles.
The values obtained for the standard cabinet models will be acceptable for
concealed models without separate tests, provided there is no variation
SECTION 15895
Page 44