in paragraph entitled "Particulate Removal Performance Guarantees." The
fabric filter baghouses will be operated on the suction side of the induced
draft fans, as indicated. Each fabric filter baghouse shall have a minimum
of four lighted modules. The modules shall be arranged in two rows with
the inlet and outlet flue gas manifolds located between the rows of
modules. The design and arrangement of the fabric filter baghouses shall
complement the spray dryer absorbers, fans and ductwork such that the
complete Flue Gas Cleaning System installation meets the space requirements
indicated. Each fabric filter baghouse shall be provided with framing for
a penthouse area as required to allow bag replacement, [damper and damper
operator maintenance] [and] [pulse valve maintenance] in a protected
paragraphs entitled "Fabric Filter Baghouses," "Structural and
Miscellaneous Steel," and in this paragraph. Submit information on the
categories general arrangement, foundation design, structural fabrication,
valves. Exterior ferrous metal surfaces of the baghouse system including,
but not limited to, fabric filter baghouse modules, hoppers, support
structures, manifolds, handrails, and kickplate shall be properly cleaned
and shop primed, as specified. Surfaces that will be exposed to the flue
gas flow need not be painted, but shall be protected during shipment and
storage with a suitable rust-preventative coating, as recommended by
manufacturer. The fabric filter baghouses shall conform to ICAC F-2, ICAC
F-3, and ICAC F-5.
2.8.1
Pulse Jet Cleaning Systems
**************************************************************************
entitled "Two-Fluid Nozzle Atomizers."
**************************************************************************
**************************************************************************
NOTE: Factors involved in selecting fabric filter
bag materials include:
1.
Duration of cleaning.
2.
Type of cleaning arrangements.
3.
System temperature level.
4.
Coal type.
5.
Sulfur dioxide removal efficiency.
NEEDLED felts are most commonly specified for
pulse-jet units. Precoat bags with fly ash prior to
operation. Fabric specifications are dependent upon
material.
**************************************************************************
**************************************************************************
NOTE: Insert appropriate Section number in the
blanks below.
**************************************************************************
The fabric filter baghouse assembly shall be of modular construction. The
inner housing casing and tube sheet of each module shall be fabricated from
SECTION 15864N
Page 44