USACE / NAVFAC / AFCESA
UFGS-15861N (September 1999)
------------------------------
Preparing Activity: NAVFAC
Replacing without revision
NFGS of same number and date
UNIFIED FACILITIES GUIDE SPECIFICATIONS
References are in agreement with UMRL dated 23 June 2005
**************************************************************************
SECTION 15861N
MECHANICAL CYCLONE DUST COLLECTOR OF FLUE GAS PARTICULATES
09/99
**************************************************************************
NOTE: This guide specification covers the
requirements for furnishing, installing, adjusting,
and testing of mechanical cyclone-type dust
collector(s).
Comments and suggestions on this guide specification
are welcome and should be directed to the technical
proponent of the specification. A listing of
technical proponents, including their organization
designation and telephone number, is on the Internet.
Recommended changes to a UFGS should be submitted as
a Criteria Change Request (CCR).
Use of electronic communication is encouraged.
Brackets are used in the text to indicate designer
choices or locations where text must be supplied by
the designer.
**************************************************************************
**************************************************************************
for flue gas particulate removal and collection
associated with coal-fired or oil-fired boilers and
refuse-fired waste disposal incinerators. Coal-fired
boilers applicable to this specification are those
designed for pulverized coal firing, spreader stoker
firing, or underfeed stoker firing with capacities
ranging between 3.78 and 44 kilogram of steam per
second 30,000 and 350,000 pounds of steam per hour.
The incinerators applicable to this specification
are those designed for burning municipal-type waste
having firing capacities between 454 kilogram per
hour 1,000 pounds per hour and 182 Mg 200 tons per
day.
**************************************************************************
**************************************************************************
NOTE: The following information shall be shown on
SECTION 15861N
Page 3