f.
Tank Outlet Capacity (design)
[_____] kg per hour.
a.
Tank Capacity (Normal-1/2 capacity)
[_____] gal.
b.
Tank Capacity (Design to overflow)
[_____] gal.
c.
Condensate Temperature
60 to 210 degrees F.
d.
Atmospheric.
e.
Tank Outlet Capacity (operating)
[_____] lb/hour.
f.
Tank Outlet Capacity (design)
[_____] lb/hour.
2.4.6
Detail Specifications
Tank shall be butt fusion welded steel plate with a maximum diameter of
[_____] and a maximum straight side length of [_____]. Tank shall be
tested under pressure to assure no leaks. Provisions shall be made in the
tank for all connections. After fabrication, the interior of the tank
shall be cleaned of all mill scale, oil, and weld splatter and then coated
with a baked-on phenolic lining or approved equivalent material that shall
be suitable and guaranteed for continuous immersion in condensate and
softened water from a sodium zeolite softener at 99 degrees C 210 degrees F.
Condensate tank shall be shop assembled and checked for proper fit of
accessories. Vendor shall determine what items should be removed and
shipped loose for field assembly. Condensate tank shall be erected in a
horizontal position.
2.4.7
Condensate Tank Trim
Condensate tank shall have the following trim:
a.
Water gauge glasses with shutoff valves to cover the full water
level travel.
b.
Thermometer.
c.
Makeup water control valve with inlet, outlet, and bypass valves.
Mechanical linkage control will not be acceptable.
d.
Pneumatic level controller.
e.
Level switches with provisions to attach an alarm or 120 volt
control signal.
f.
g.
Insulation clips for 25 mm 1 inch block insulation.
h.
All controllers, alarms, gauges, sight glasses, control valves,
etc., shall be provided with shut off and/or bypass valves as
required for maintenance of the system while in operation.
2.4.8
Additional Requirements
All required foundations, anchor bolts, concrete work, and grouting shown
in the manufacturer's load diagram and anchor bolt plan shall be provided.
Insulation and covering shall conform to Section 15080A THERMAL INSULATION
SECTION 15846A
Page 40