supplier shall submit to the Contracting Officer satisfactory evidence that
the fan furnished meets the requirements of AMCA 210. Acceptable evidence
of meeting the requirements of this standard will be the AMCA Certified
Rating Seal or a certified inspection report from an independent testing
laboratory indicating that the fan conforms to the requirements of AMCA 210.
Fans shall be centrifugal with backward curved blades or radial tip
blades. Each fan shall be sized for operation at an elevation of [_____]
meters feet, with an output volume and equipment, leaks, and temperature
and elevation corrections for a dirty boiler with worst ambient conditions,
all at full combustion. In addition, fan sizing shall include margins of
10 percent excess volume against a 21 percent static pressure and air
temperature 22 degrees C 40 degrees F above operating temperature. Induced
draft fans shall be designed for handling hot flue gas at the maximum
boiler outlet temperature adjusted for boiler surface fouling. Fans shall
be of the [single] [or] [double] width centrifugal type. [When the fan is
a double-width centrifugal type, it shall have a double inlet.] The
direction of fan rotation shall be [clockwise] [or] [counterclockwise] as
determined from the drive side of the fan. The direction of discharge
shall be [top horizontal] [top angular down] [down blast] [bottom angular
down] [top angular up] [up blast] [bottom angular up] [or] [bottom
horizontal]. The position of inlet box shall be [45] [90] [135] [180]
[225] [270] [315] [or] [360]. The fans shall have a static efficiency of
not less than 0 percent in standard air at best efficiency point. Fan
wheel shall be constructed of [steel] [or] [aluminum]. The shaft shall be
turned, ground, and polished. The fan wheel and shaft assembly shall be
balanced statically and dynamically. The complete rotating assembly of the
fan shall be dynamically balanced within the limits of the following
formula:
Vibration displacement
-
1.620
__________________________
mills-peak-to-peak
revolutions per minute
Noise levels for fans shall not exceed 85 dBA at a 914.4 mm 3 foot station.
The fan housing shall be carbon steel of a nominal thickness not less than
that selected in Table I.
TABLE I
HOUSING GAUGES
Nominal fan diameter
Sides
Scroll in inches
____________________________________________________________________________
up to 23
3.42 mm (10 gauge)
3.42 mm (10 gauge)
24-27
4.55 mm (7 gauge)
4.55 mm (7 gauge)
73-over
6.35 mm (1/4 inch)
6.35 mm (1/4 inch)
TABLE I
HOUSING GAUGES
Nominal fan diameter
Sides
Scroll in inches
____________________________________________________________________________
up to 23
10 gauge
10 gauge
24-27
7 gauge
7 gauge
73-over
1/4 inch
1/4 inch
Scroll and sideplate joints shall be continuously welded. The housing
shall be reinforced with steel member to provide a rigid structure and to
SECTION 15846A
Page 32