3.2.1
Field Inspection
with drawings and specifications.
3.2.2
Test 600-volt wiring to verify that no short circuits or grounds exist.
Tests shall be made using an instrument which applies a voltage of
approximately 500 volts and provides a direct reading of resistance in ohms.
3.2.3
Test equipment circuits and devices to demonstrate proper operation.Test
each item of control equipment not less than 5 times.
SECTION 15768N
Page 10