Submittal items not designated with a "G" are
considered as being for information only for Army
projects and for Contractor Quality Control approval
for Navy projects.
**************************************************************************
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are [for Contractor Quality Control
approval.][for information only. When used, a designation following the
"G" designation identifies the office that will review the submittal for
the Government.] The following shall be submitted in accordance with
Section 01330 SUBMITTAL PROCEDURES:
SD-03 Product Data
**************************************************************************
Note: Indicate sound ratings or loudness level of
equipment in the Equipment Schedule on the drawings.
**************************************************************************
Desiccant Dehumidification Unit
SD-06 Test Reports
Filter sections
Preliminary tests
Dampers leakage test
SD-07 Certificates
Desiccant dehumidification unit
SD-10 Operation and Maintenance Data
Desiccant dehumidification unit, Data Package 5
Submit in accordance with Section 01781 OPERATION MAINTENANCE
DATA.
PART 2
PRODUCTS
2.1
DESICCANT DEHUMIDIFICATION UNIT
2.1.1
Air Handling Components
All air handling components of the desiccant dehumidification unit
([casing,] [dampers,] [fans] [vibration isolation,] [filter sections,]
[mixing boxes,] [outside air intake,] [[heating] [cooling] sections] [roof
curbs] [and] corrosion criteria as applicable) shall meet the requirements
of Section 15720N AIR HANDLING UNITS. Units shall include humidity
controls (humidistat) and temperature controls (thermostat).
[2.1.2
Hot Water Heater
Hot water heater shall meet the requirements of Section 15514N LOW PRESSURE
WATER HEATING BOILERS UNDER 800,000 BTU/HR OUTPUT, with an atmospheric-type