j.
Finish: Apply corrosion protection system to the outside of
galvanized surfaces. Construct non-stainless metal components of
mill hot-dip galvanized steel. Coat component edges and welds
with a 95 percent pure zinc-rich compound. Preparation for
coating shall include degreasing, cleaning, and a light surface
burnishing. The coating shall be suitable for field repair with
the same original coating material applied in the same manner.
k.
Electric Pan Heater Package: Electric pan heater package consists
of electric immersion heaters, heater thermostat, and low water
cutout, all installed in pan. Size heaters to maintain +5 degrees
C +40 degrees F pan water temperature with the fans off at design
conditions indicated on drawings. Control the heaters with a
thermostat, and provide water cutout to prevent heaters from
cycling on unless they are completely submerged. Provide heater
contactor and wiring under Section 16402 INTERIOR DISTRIBUTION
SYSTEM.
l.
Discharge Hood With Positive Closure Dampers: Provide unit with
discharge hood, positive closure dampers, and 120-volt actuator
for reduction of heat loss during idle periods of winter time
operation. Construct the discharge hood and dampers of hot dipped
galvanized steel. Equip hoods with access panels to facilitate
maintenance on the eliminators and water distribution system.
Factory assemble the dampers, damper actuator, and linkage.
]2.1.4
**************************************************************************
NOTE: Plate heat exchangers are required in systems
isolate the ground heat exchanger loops from the
building terminal loops.
**************************************************************************
**************************************************************************
NOTE: Provide the following flat plate heat
exchanger information on the drawing:
1. Maximum water pressure drop through clean plates
and headers in kPa psi at the flow rates and
temperatures indicated.
2. Minimum rate of turbulent flow in l/sec gpm
through any two plate segment.
3. Minimum plate thickness in mm inch.
**************************************************************************
Plates, frames, and gaskets shall be designed for a working pressure of
2.07 MPa 300 psi and factory tested at 31.0 MPa 450 psi. Medium
temperature water, low temperature water, and pressure relief valve
connections shall be located in accordance with the manufacturer's standard
practice. Connections larger than 80 mm 3 inches shall be ASME 2.07 MPa
300 pound flanged. Plates shall be corrugated [Type 304 stainless steel]
[Type 316 stainless steel] [nickel-iron-chromium alloy conforming to ASTM B
424] [nickel-molybdenum alloy conforming to ASTM B 333] [titanium alloy
conforming to ASTM B 265].