noncondensable gases from refrigeration system and condense, separate, and
return to system refrigerant present. Provide an oil separator, if
required by manufacturer. Purge systems shall provide a warning to signal
operator at occurrence of excessive purging, indicating abnormal air
leakage into unit. Purge systems shall not discharge to occupied areas, or
create a potential hazard to personnel.
2.1.1.6
Evacuation or Pump-Out Systems
When a positive refrigerant is used and basic chiller unit will not permit
pumpdown storage and isolation of entire charge within basic unit, provide
a manually started and stopped evacuation or pump-out system, consisting of
a condensing unit and a receiver of sufficient capacity to store entire
refrigerant charge of largest water-chilling system or unit. When designed
to permit pumpdown of entire refrigerant charge and isolation of entire
refrigerant charge within basic unit, a separate evacuation or pump-out
shall not be required. Receivers shall be provided with rupture members
and dual relief valves, piping, and controls so that the evacuation or
pump-out system may be provided without temporary piping or wiring.
2.1.1.7
Controls, Control Panels, and Gages
**************************************************************************
NOTE: Specify required time delay for type and size
of unit after consulting current literature.
**************************************************************************
**************************************************************************
NOTE: Include sentence in brackets if centrifugal
chillers are specified.
**************************************************************************
Provide an automatic capacity-reduction system for stable operation from
100 to 10 percent of full load capacity. Provide modulating, chilled-water
controls with adjustable throttling range, a means of calibration, and a
means of adjusting chilled-water temperature control point. Provide a time
delay of not less than [_____] minutes to prevent compressor restart when a
compressor is shut down by the operating controls. Provide a demand
limiter to minimize amperage draw. [Provide controls to restart chiller
automatically if power is interrupted for three seconds or less.] Provide
a control panel complete with compressor operating control, start-stop
a.
Gages:
(1)
(2)
(3)
Oil pump pressure
(4)
Elapsed running time meter
b.
(1)
Low oil temperature lockout
(2)
Low refrigerant temperature cutout
SECTION 15601N
Page 14