air and heat penetration capacity at floor level based on established
design temperature. Suspension from heating pipes will not be permitted.
Fans for vertical discharge type heaters shall operate at speeds not in
excess of 1,200 rpm, except that units with 53 Megajoules (50,000 Btu)
50,000 Btu output capacity or less may operate at speeds up to 1,800 rpm.
Horizontal discharge type unit heaters shall have discharge or face
velocities not in excess of the following:
Unit capacity, liters
Face velocity, meters
per second
per second
Up to 472
4.1
473-1400
4.6
1401 and over
5.1
Unit capacity, cfm
Face velocity, fpm
Up to 1,000
800
1,001 to 3,000
900
3,001 and over
1,000
2.4.2.2
Centrifugal Fan (Type II) Heaters
Heaters shall be arranged for floor or ceiling mounting. Heating elements
and fans shall be housed in steel cabinets of sectionalized steel plates or
reinforced with angle-iron frames. Cabinets shall be constructed of not
lighter than 1.214 mm (18 gauge) 18 gauge black steel. Each unit heater
shall be provided with a means of diffusing and distributing the air. Fans
shall be mounted on a common shaft, with one fan to each air outlet. Fan
shaft shall be equipped with self-aligning ball or roller bearings and
accessible means of lubrication. Fan shaft may be either directly
connected to the driving motor or indirectly connected by adjustable V-belt
drive rated at 150 percent of motor capacity. Fans in any one unit heater
shall be the same size.
2.4.2.3
Heating Elements
Heating coils and radiating fins shall be of nonferrous alloy. Heating
elements shall be free to expand or contract and shall be pitched for
drainage. Elements shall be tested under a hydrostatic pressure of 1.4 MPa
200 psig.
2.4.2.4
Motors
Motors shall be provided with manual selection switches for
[On-Off-Automatic] [On-Off] [High/Low-Off] operation and shall be equipped
with thermal overload protection.
2.4.3
Heating and Ventilating Units
**************************************************************************
NOTE: Indicate capacity of unit heaters and heating
and ventilating units on drawings.
**************************************************************************
Units shall be ceiling- or floor-mounted type, self-contained, with the
heating coils, fans, dampers, and filters completely encased in a steel
housing of sectionalized steel plates or reinforced with an angle-iron
frame. Each unit shall be provided with latched, removable access panels