As a minimum, the following parameters shall be displayed on the panel:
Pressure
Indicator
Recorder Point
Main steam header
X
X
Boiler drum
X
Feedwater
X
X
Instrument air
X
Draft
Indicator
Recorder Point
Windbox
X
Furnace
X
Boiler gas outlet
X
ID fan inlet
X
Temperature
Indicator
Recorder Point
Main steam
X
Boiler gas outlet
X
Windbox
X
Feedwater
X
Level
Indicator
Recorder Point
Boiler drum
X
Bunker or silo
X
Flow
Indicator
Recorder Point
Main steam (including
totalizer)
X
Feedwater
X
Air
X
Fuel
X
Analyzers
Indicator
Recorder Point
Flue gas opacity
X
Flue gas oxygen
X
2.8.5
Panel Piping and Wiring
High-pressure and high temperature values shall be pneumatically or
electrically transmitter, or both, to the panel. Pneumatic signals shall
be 21 to 103 kPa 3 to 15 psig. Piping connectors to indicators shall be 6
mm 1/4 inch OD copper tubing conforming to ASTM B 68M ASTM B 68. Flow
signals shall be transmitted either pneumatically or electrically to the
panel-mounted receiver. Copper tubing connections and electric wiring
shall be run to a terminal block located on the inside of the panel front
near the bottom. Wiring shall be terminated at an identified terminal
strip. Wiring shall be suitable for boiler room requirements and installed
according to NFPA 70.
2.8.6
Pilot Lights
Pilot lights shall be assembled in a factory-built cabinet, suitable for
flush mounting in cutouts in boiler control panel, complete with extruded
trim, clamps, and sheet metal rear housing, and finished in baked black
SECTION 15559A
Page 53