Condensate
Makeup Water
Valve size
[______] mm
[______] mm
Capacity
[______] L/s
[______] L/s
Maximum pressure drop
[______] kPa (gage) [______] kPa (gage)
at above capacity
Available pressure
[______] kPa (gage) [______] kPa (gage)
Minimum Cv at
[______]
[______]
100 percent open
Condensate
Makeup Water
Valve size
[______] inch
[______] inch
Capacity
[______] gpm
[______] gpm
Maximum pressure drop
[______] psig
[______] psig
at above capacity
Available pressure
[______] psig
[______] psig
Minimum Cv at
[______]
[______]
100 percent open
2.9.2.10
Low Pressure Steam Control
Provide an automatic control system to control the steam to the deaerating
heater. Maintain steam pressure in the heater by modulating a pressure
reducing valve in the steam supply line. Control shall be local and remote
from the control panel.
a.
Controller: Adjustable proportional band, 0 to 103 kPa (gage) 15
psig brass bellows for input signal, and 20 to 103 kPa (gage) 3 to
15 psig output air pressure range, pilot controller complete with
control valve yoke.
b.
Pressure Reducing Station Control Valve: Provide a [_____] mm inch
air operated pressure reducing valve with proper internals to
pass a flow of [_____] kg per second pounds per hour of steam.
Steam at the valve inlet shall be [_____] kPa (gage) psig
saturated, and the outlet shall be controlled at [_____] kPa (gage)
psig. Minimum steam flow shall be approximately [____] kg per
second pounds per hour. Minimum valve Cv shall be [_____] at 100
percent open. Valve shall be Class 250 or Class 300 flanged, iron
or semi-steel body with stainless steel internals equal percentage
flow characteristics and a full size port. Provide valve actuator
including travel indicator, hand jack, valve positioner, and air
supply filter-reducer set. Valve shall move to open position in
case of failure.
2.9.2.11
Provide gage glasses to cover the entire range of water level in the
SECTION 15511N
Page 53