ratings. Make modifications and additions to the system to ensure
penetration and turbulence of areas of the furnace as required after
startup. [There will be no cinder return system incorporated in the
overfire air system.]
**************************************************************************
NOTE: At the text below, delete the following
paragraph on pneumatic cinder return (fly ash
reinjection) system when this system will not be
incorporated in the project.
**************************************************************************
[a.
Cinder Return System (Fly Ash Reinjection): Provide a pneumatic
cinder return system to reinject collected fly ash and unburned
combustibles into the furnace. The system shall operate in
conjunction with the overfire air system and shall be complete
with necessary air lines, nozzles, ducts, and dampers for
returning the cinders from the rear convection pass hopper of the
boiler and the economizer soot hopper or air heater hopper.
Cinder return lines, shall be constructed of abrasion-resistant
iron having a Brinnell hardness of not less than 350, with the
exception that the straight conveyor lines, starting at a point
not less than 600 mm 2 feet downstream from each cinder pickup
nozzle or elbow extending to within not less than 600 mm 2 feet of
the furnace, may be constructed of extra strong Schedule 80 steel
pipe. Provide glass viewing ports at the end of each cinder
return line so that interior of lines are visible all the way
through to furnace.]
]2.5
OIL BURNER/WINDBOX PACKAGE
**************************************************************************
NOTE: Choose this paragraph and its subparagraphs
when oil is used.
**************************************************************************
**************************************************************************
NOTE: The designer shall fill in the appropriate
information as defined in MIL-B-18796.
**************************************************************************
Provide a fully modulating, oil burner conforming to MIL-B-18796 Rev F,
Class [_____], except as modified below. Provide burner with windbox,
forced draft fan, dampers, fuel train and associated controls to comprise a
complete factory assembled package. Total heat input to boiler furnace
shall be provided by [_____] burners. Burner package shall be considered
an integral part of the steam generator and shall be subject to applicable
provisions of the boiler design and service together with requirement of
tests, performance guarantees and other warranties specified for the boiler.
2.5.1
Burner
2.5.1.1
Burner Characteristics
The burner shall be quiet in operation and operate with a balanced clean,
stable flame so as not to localize heat in any part of the combustion
chamber. Burner shall be capable of completely atomizing and effectively
mixing oil with air so as to ensure complete combustion. Air admitted
shall be of sufficient quantity for complete combustion, but not of such
SECTION 15502N
Page 70