USACE / NAVFAC / AFCESA
UFGS-15502N (June 2005)
------------------------------
Preparing Activity: NAVFAC
Superseding
UFGS-15502N (September 1999)
UNIFIED FACILITIES GUIDE SPECIFICATIONS
Latest change indicated by CHG tags
References are in agreement with UMRL dated 23 June 2005
**************************************************************************
SECTION 15502N
STEAM HEATING PLANT WATERTUBE (FIELD ERECTED) COAL/OIL OR COAL
06/05
**************************************************************************
NOTE: This guide specification covers the
requirements for steam heating plants from 7 1/2 to
60 1/2 kg/sec 60,000 to 480,000 lbs/hr steam
capacity using a field erected watertube boiler.
Comments and suggestions on this guide specification
are welcome and should be directed to the technical
proponent of the specification. A listing of
technical proponents, including their organization
designation and telephone number, is on the Internet.
Recommended changes to a UFGS should be submitted as
a Criteria Change Request (CCR).
Use of electronic communication is encouraged.
Brackets are used in the text to indicate designer
choices or locations where text must be supplied by
the designer.
**************************************************************************
**************************************************************************
NOTE: This guide specification covers requirements
for equipment for a steam heating plant which will
generate from 7 1/2 to 60 1/2 kg of steam per second
60,000 to 480,000 pounds of steam per hour. This
specification is intended to be used in the
procurement and installation of heating plant
equipment. Requirements for materials and
procedures for special or unusual design shall be
added to and modifications made to this
specification as necessary to fit specific projects.
This guide specification shall be used in
conjunction with the following NAVFAC definitive
drawings:
NAVFAC NO./DRAWING TITLE
1429345 - STEAM HEATING PLANT NO.5 7 1/2 - 34 kg/sec
SECTION 15502N
Page 12