uuuu. Item P8700. Washer, tubing with individually controlled
connectors for tubing 6 to 15 mm 1/8 to 1/2 inch inside diameter
and number of outlets as indicated. Tubing washers shall consist
of four serrated nozzles, each equipped with backflow preventers
and individual volume control valves with 15 mm 1/2 inch hot and
cold water valved controls to the assembly. Washer shall be
constructed of brass chromium plated. Hose nozzles shall be
suitable for hoses ranging in size from 6 mm 1/8 inch and shall
have a 10-serration hose end. Backflow preventers shall be of the
moving part and air vent type. Control valve for nozzles shall be
not less than 152 mm 6 inches on center.
vvvv. Item P9000. Water closet wall-hanging, siphon-jet, elongated
bowl for direct flushometer valve, shall conform to ASME A112.19.2M.
Seat shall conform to ANSI Z124.5, SPN CEWX. Flushometer valve
shall conform to ASSE 1037, SPN 1a3.5. The maximum water use
allowed shall be 6 L 1.6 gallons per flush. Floor flange shall be
[cast iron] [copper] [or] [copper alloy], with wax seal unless
otherwise specified.
wwww. Item P9050. Water closet floor mounted, siphon-jet, elongated
bowl shall conform to ASME A112.19.2M. Seat shall conform to ANSI
Z124.5, SPN CEWX. Flushometer valve shall conform to ASSE 1037,
SPN 1a3.5. The maximum water use allowed shall be 6 L 1.6 gallons
per flush. Floor flange shall be [cast iron] [copper] [or]
[copper alloy], with wax seal unless otherwise specified.
xxxx. Item P9150. Cabinet, toilet/lavatory cabinet. Lavatory/toilet
combination unit shall have 304 stainless steel cabinet frame,
elongated siphon jet toilet and lavatory. Cabinet doors shall
support 1.1 kN 250 pound static load and floor-supported toilet
shall support 11 kN 2500 pound static load. Cabinet and
countertop shall be melamine plastic laminate. Valves shall be
wrist handle or foot control as required.
yyyy. Item P9160. Lavatory, disturbed patient, shall consist of
vitreous china, with integral faucet and soap dish, and
self-closing pushbutton valves. Flow shall be limited to 1 L 0.25
gallon per cycle at a flowing water pressure of 549 kPa 80 psi if
a metering device or fitting is used that limits the period of
water discharge such as a foot switch or fixture occupancy sensor.
If a metering device is not used, the flow shall be limited to
0.16 L/second 2.5 gpm at a flowing water pressure of 549 kPa 80 psi.
zzzz. Item P9180. Lavatory, wheelchair, 508 x 686 mm 20 x 27 inches
with appropriate carrier for installation.
aaaaa. Item P9200. Water closet floor mounted, regular bowl, wash-
down, shall conform to ASME A112.19.2M. Seat shall conform to
ANSI Z124.5, SPN CRWX. Flushometer valve shall conform to ASSE
1037, SPN 1a3.5. The maximum water use allowed shall be 6 L 1.6
gallons per flush. Floor flange shall be [cast iron] [copper]
[or] [copper alloy], with wax seal unless otherwise specified.
bbbbb. Item P9320. Floor drain attachment, used in hydrotherapy
rooms shall have automatic trap primer.
ccccc. Item P9400. Water closet, NP Patient, shall conform to ASME
A112.19.2M, SPN SJEB203. Seat shall conform to ANSI Z124.5, SPN
SECTION 15405A
Page 43