design pressure.
Snubber element:
sintered stainless steel or other
approved type.
2.9.10
Timed Solenoid Drain
Packaged solenoid drain with 6 mm, [20,682] [34,470] kPa (gage) 1/4 inch,
[3000] [5000] psig, direct acting, normally closed solenoid valve, solid
state timer, drain cycle adjustable from zero to 50 minutes, valve open
duration adjustable from one to 14 seconds, power on light, valve open
light, operation on 115 or 230 VAC, and housed in NEMA [1] [_____]
enclosure.
2.9.11
Filter housing of [Type [304L] [316L] stainless steel] [70-30
copper-nickel] [70-30 nickel-copper] construction. Provide a cellulose
cartridge filter of graded density construction capable of removing liquids
and solids of 5 microns and larger. Provide filter with a bottom drain and
2.9.12
Strainers
Y-pattern type with [cast stainless steel body, ASTM A 351/A 351M CF8M
(Type 316), CF8 (Type 304), CF3 (Type 304L) or CF3M (Type 316L,] [70-30
copper-nickel,] [70-30 nickel-copper,] [forged alloy steel body ASTM A
182/A 182M, Grade F-22,] rated for the system design working pressure, with
20-mesh Monel or stainless steel screen. Net strainer area not less then
2.5 times the inlet connection area.
2.9.13
Unions
O-ring seal type compatible with union ends of MIL-V-24109 valves, material
and end preparation compatible with pipe and fittings.
2.9.14
O-Ring Gaskets
SAE AMS7276.
2.9.15
Hangers and Supports
Provide pipe hangers and supports conforming to MSS SP-58, MSS SP-69, and
ASME B31.1, except as specified or indicated otherwise. Hangers for high
pressure air lines shall be rigid or braced and sufficiently strong to
prevent "whipping" of a pipe if a break occurs while the line is under
pressure. Furnish zinc plated pipe hangers and supports except for copper
plated inserts for copper piping. Provide tubing supports of U-shaped
steel bolts and nuts firmly secured to adequately support structures such
as walls, columns, floors, or brackets. Clips shall fit closely around
piping but shall have sufficient clearance to permit longitudinal movement
of piping during normal expansion and contraction. Provide supports at
valves, fittings, branch lines, outlets, changes in direction, equipment,
and accessories.
2.10
MEDIUM PRESSURE COMPRESSED AIR PIPING AND ACCESSORIES
**************************************************************************
NOTE: Components are listed based on operation at
SECTION 15212N