Air dryer, Data Package 4
Submit in accordance with Section 01781 OPERATION AND
MAINTENANCE DATA.
SD-11 Closeout Submittals
Posted operating instructions for air dryer
1.4
QUALITY ASSURANCE
**************************************************************************
NOTE: The SMACNA Seismic Restraint Manual
referenced in the paragraph below shall be applied
to locations subject to significant risk of seismic
induced loads. The degree to which this manual is
to be used for contract drawings and specifications
shall be determined by the designer of record in
coordination with the NAVFAC Engineering Field
Division's Mechanical Design Branch.
**************************************************************************
Provide all work specified in this section, including design, materials,
fabrication, assembly, erection, installation, and examination, inspection
BPVC SEC VIII D1 [and ASME BPVC SEC IX] [ ASME BPVC SEC IX and SMACNA
Seismic Restraint Mnl], as modified and supplemented by this specification
section and accompanying drawings. In ASME B31.1, ASME BPVC SEC VIII D1
and ASME BPVC SEC IX, the advisory provisions shall be considered
mandatory, as though the word "shall" had been substituted for "should"
wherever it appears; reference to the "authority having jurisdiction" and
"owner" shall be interpreted to mean the Contracting Officer.
1.4.1
Submit the following data for equipment listed for "Operation and
Maintenance Instructions, Parts and Testing."
a.
Name and address of authorized branch or service department.
b.
Characteristic curves.
c.
Following applicable data completely filled in:
Manufacturer and model number
[_____]
Operating speed
[_____]
Capacity [_____] (CMS) (CFM)
[_____]
Type of lubrication
[_____]
Type and adjustment of drive
[_____]
SECTION 15212N
Page 12