2.14.1
Door Panel
ASTM E 2074, fire rated door panel, with minimum 100 mm wide by 225 mm high
4 inch wide by 9 inch high vision panel at upper door section.
2.14.2
Door Operation
**************************************************************************
NOTE: Use semi-selective if only one opening at any
floor; full-selective if two openings at any floor.
**************************************************************************
[Semi-selective] [Full-selective].
2.15
HANDICAPPED AND MEDICAL SERVICES ACCESS
2.15.1
Provision For Handicapped
**************************************************************************
**************************************************************************
36 CFR 1191, Sections 4.10 for Elevators, 4.30 for Signage, and 4.31 for
Telephones.
2.15.2
Emergency Medical Service
**************************************************************************
NOTE: Use this paragraph for buildings of four
floors or more.
**************************************************************************
ICC IBC - Chapter 30, for elevators and signage
2.16
EMERGENCY POWER OPERATION
**************************************************************************
NOTE: Use in hospitals and buildings in which
sufficient standby power is provided to operate one
or more elevators.
**************************************************************************
Upon outage of normal power and initiation of emergency power, provide
circuitry and wiring to operate elevator [telephone] [and] [intercom] to
accomplish operation sequences. [In multiple elevator system, one elevator
travels automatically to the main floor, opens doors, and shuts down.
Thereafter, each other elevator in group, one at a time returns
automatically to main floor. After all cars have returned to main floor,
provide automatically one [passenger] [freight] car in regular service.]
[For single elevator system, elevator travels automatically to main floor,
opens doors, and automatically places itself in regular service.] During
emergency power operation, provide a sign reading "EMERGENCY POWER"
flashing in each car station. [At the same time, provide operable
Firefighters' Service.]
2.17
PROVISIONS FOR EARTHQUAKE PROTECTION
**************************************************************************
SECTION 14240
Page 32