visual alarms outside entrances to protected areas, and provide with
warning signs reading "CARBON DIOXIDE DISCHARGED WHEN FLASHING - DO NOT
ENTER."]
2.10.1
Alarm Bells
[Surface mounted] [Recessed], [250 mm] [10 inch] [_____] diameter with
matching mounting back box. Provide vibrating type bells suitable for use
in an electrically supervised circuit. Provide underdome type bells which
produce a sound output rating of at least 87 decibels at 3 meters 10 feet.
Finish bells in red enamel.
2.10.2
Alarm Horns
[Surface Mounted] [Recessed], vibrating type suitable for use in an
electrically supervised circuit and with a sound output rating of at least
87 decibels at 3 meters 10 feet. Finish horns in red enamel.
2.10.3
Visual Alarms
[Surface] [Flush] mounted lamp assembly suitable for use in an electrically
supervised circuit. Provide flashing [stroboscopic] [incandescent] [rotary
beacon] lamps, powered from the control panel alarm circuit. Use lamps
with a minimum of 50 candle power. Ensure flash rate is between 60 and 120
flashes per minute. Protect lamps with a thermo-plastic lens, red for
pre-discharge alarms and blue for discharge [and post-discharge] alarms.
[Visual alarms may be part of an audio-visual alarm assembly.]
2.11
MAIN ANNUNCIATOR
separate alarm and trouble lamps for each zone alarm initiating circuit
located on exterior of cabinet door or visible through cabinet door.
Supervision will not be required provided a fault in annunciator circuits
results only in loss of annunciation and not affect normal functional
operation of remainder of system. Identify the specific [zone] [area]
[device] of each lamp by means of a permanent label. Do not use zone
identification consisting of such words as "Zone 1," "Zone 2;" use a
description of [zone] [area] [device].
2.11.1
Annunciation Zones
Arranged as follows:
Zone 1:
[_____]
Zone 2:
[_____]
Zone 3:
[_____]
Zone X:
[_____]
2.11.1.1
Remote Annunciator Panel
Locate as shown. Provide panel which duplicates requirements specified for
trouble lamps a single trouble lamp may be provided. Provide panel with a
lamp test switch. Identify zones by means of [permanently attached rigid
plastic or metal plates] [silk-screened labels attached to reverse face of
SECTION 13962N
Page 22