UNDERWRITERS LABORATORIES (UL)
UL 262
Service
UL 789
(2004) Indicator Posts for Fire-Protection
Service
UL Fire Prot Dir
(2004) Fire Protection Equipment Directory
1.2
DEFINITION
a.
Year 2000 compliant - means computer controlled facility
components that accurately process date and time data (including,
but not limited to, calculating, comparing, and sequencing) from,
into, and between the twentieth and twenty-first centuries, and
the years 1999 and 2000 and leap year calculations.
1.3
RELATED REQUIREMENTS
Section 15050N BASIC MECHANICAL MATERIALS AND METHODS, applies to this
section, with the additions and modifications specified herein.
1.4
SYSTEM DESCRIPTION
1.4.1
**************************************************************************
NOTE: Identify the rooms, spaces or areas, as
appropriate, which are to be protected by each
system.
**************************************************************************
**************************************************************************
NOTE: Include only those NFPA codes applicable to
the specific project.
**************************************************************************
Design and [provide a new] [and] [modify an existing] automatic aqueous
film forming foam (AFFF) [pre-action] [dry-pipe] [deluge] sprinkler
system(s) for [_____]. System shall provide uniform distribution of AFFF
solution to provide complete coverage throughout the [building] [areas
indicated]. The design, equipment, materials, installation, and
workmanship shall be in strict accordance with the required and advisory
provisions of NFPA 11, NFPA 13, [NFPA 14,] [NFPA 15,] [NFPA 16,] [NFPA 24,]
[NFPA 30,] NFPA 70, NFPA 72, [NFPA 231C,] except as modified herein. Each
system [shall be designed for earthquakes and] shall include all materials,
accessories and equipment necessary to provide each system complete and
ready for use. Design and install each system to give full consideration
to blind spaces, piping, electrical equipment, ductwork, and all other
construction and equipment to provide complete coverage in accordance with
the drawings to be submitted for approval. Devices and equipment for fire
protection service shall be of a make and type listed by the Underwriter's
Laboratories Inc. in the UL Fire Prot Dir, or approved by the Factory
Mutual System and listed in FM P7825. In the publications referred to
herein, the advisory provisions shall be considered to be mandatory, as
though the word "shall" had been substituted for "should" wherever it
appears; reference to the "authority having jurisdiction" shall be
interpreted to mean the [[_____] Division, Naval Facilities Engineering
SECTION 13958N
Page 8