SD-07 Certificates
UL listing or label; G
1.4
QUALITY ASSURANCE
In each standard referred to herein, consider the advisory provisions to be
mandatory, as though the word "shall" has been substituted for "should"
wherever it appears. Interpret references in these standards to "authority
having jurisdiction," or words of similar meaning, to mean Contracting
Officer.
1.4.1
Installation Drawings
a.
system. Drawings shall include physical layout of the equipment,
mounting details, relationship to other parts of the work, and wiring
diagram.
b.
manufacturer's descriptive and technical literature, catalog cuts, and
1.4.2
UL Listing or Label
Submit proof of compliance. Label of or listing in UL Elec Const Dir is
acceptable evidence. In lieu of label or listing, submit written
certificate from an approved, nationally recognized testing organization
equipped to perform such services, stating that items have been tested and
conform to requirements and testing methods of Underwriters Laboratories.
1.5
SITE CONDITIONS
Contractor will become familiar with details of the work, verify dimensions
in the field, and advise Contracting Officer of discrepancies before
performing work. Deviations from contract drawings will not be made
without prior approval of Contracting Officer.
PART 2
PRODUCTS
2.1
MATERIALS
Do not use a combination of materials that forms an electrolytic couple of
such nature that corrosion is accelerated in presence of moisture unless
moisture is permanently excluded from the junction of such metals. Where
unusual conditions exist which would cause corrosion of conductors, provide
conductors with protective coatings or oversize conductors. Where
mechanical hazard is involved, increase conductor size to compensate for
hazard or protect conductors by covering them with molding or tubing made
of wood or nonmagnetic material. When metallic conduit or tubing is
provided, electrically bond conductor to conduit or tubing at the upper and
lower ends by clamp type connectors or welds (including exothermic).
2.1.1
NFPA 780 and UL 96 Class I, Class II, or Class II modified materials as
SECTION 13100N
Page 6