2.5.7.1
Swinging Door Static Load Test
The door shall be mounted and latched to its frame, then set down in a
horizontal position such that it will open downward with only the frame
rigidly and continuously supported from the bottom. A load of 195 kg/psm
40 lb/psf shall be applied uniformly over the entire surface of the door
for at least 10 minutes. The door will not be acceptable if this load
causes breakage, failure, or permanent deformation which causes the
clearance between door leaf and stops to vary more than 1.6 mm 1/16 in from
the original dimension.
2.5.7.2
Swinging Door Sag Test
The door and its frame shall be installed normally and opened 90 degrees.
Two 45 kg 100 pound weights, one on each side of the door, shall be
suspended from the door within 130 mm 5 in of the outer edge for at least
10 minutes. The door will not be acceptable if this test causes breakage,
failure, or permanent deformation which causes the clearance between the
door leaf and door frame to vary more than 1.6 mm 1/16 in from the original
dimension.
2.5.7.3
Door Closure Test
Each door design shall be operated 100,000 complete open-close cycles. The
door will not be acceptable if the closure test causes any breakage,
failure, or permanent deformation which causes the clearance between the
door and door frame to vary more than 1.6 mm 1/16 in from the original
dimension.
2.5.7.4
Handle-Pull Test
The door shall be mounted and latched to its frame. The handle shall have
a force of 1100 N 250 pounds applied outward (normal to the surface of the
door) at a point within 50 mm 2 in of the end of the handle. The door will
not be acceptable if this test causes any breakage, failure, or permanent
deformation exceeding 3 mm 1/8 inch.
2.5.7.5
Door Electromagnetic Shielding Test
The EM shielded door shall be factory tested in accordance with the
requirements of this specification both before and after the mechanical
tests described above.
2.6
ELECTROMAGNETIC FILTERS
**************************************************************************
NOTE: All EM filters for power and signal lines
should be scheduled on the drawings.
This guide specification covers electromagnetic
filters for 50, 60, and 400 Hz power lines and
signal lines for General Use Only. This
specification is NOT applicable for filters to be
used with a specific individual item of electronic
equipment. Filters for use with specific individual
items of equipment must be scheduled on the drawings
showing voltage, current, insertion loss, passband,
**************************************************************************
SECTION 13095A
Page 27