catalog number, model, style, and type on a plate securely and
conspicuously attached to each item of equipment. Nameplates for
electrical apparatus shall conform to NEMA Standards.
2.10
LIGHTING
**************************************************************************
NOTE: In shielded enclosures where electronic
equipment is very sensitive to EMI, specify a dual
turned off and incandescent lighting left on during
sensitive tests or operations.
**************************************************************************
requirements of MIL-STD-461, Class C3, Group I for both conducted and
2.11
**************************************************************************
NOTE: This paragraph cites only minimum
requirements. Design calculations are necessary to
size HVAC to suit room size and equipment/personnel
contained within. Exhaust fan motors located inside
shielded enclosure must meet MIL-STD-461, Class C3,
Group I.
**************************************************************************
FS A-A-50032, Type I, Class 1 for direct drive, Class 2 for belt drive,
Style A for wall or window mounting, Style B for roof or ceiling mounting,
except that fans shall be centrifugal type with aluminum housing and wheel.
requirements of FS A-A-50032. Motors shall be completely shielded from the
air stream. Provide exhaust opening and gravity closing type automatic
louvers. Provide exhaust which can supply 15 room air changes per hour.
Capacity of fans shall be certified in accordance with AMCA 210, and shall
be not greater than 110 percent of the indicated capacity at indicated
pressure drop.
2.12
COAXIAL CABLE PENETRATIONS
For each coaxial cable entering the shielded enclosure, provide RF
waveguide threaded insert with cap and chain on shielded room side of
enclosure.
2.13
SOURCE QUALITY CONTROL
**************************************************************************
NOTE: When specifying nonlatching doors, delete
door static load and sag tests and cycle test for
door latches. Retain cycle test for door hinges.
**************************************************************************
2.13.1
Door Static Load Test
The door shall be mounted and latched to its frame, then set down in a
horizontal position such that the door will open downward and only the
SECTION 13093N
Page 14