the submittal tags may be used following the "G"
designation to indicate the approving authority.
Codes for Army projects using the Resident
Management System (RMS) are: "AE" for
Architect-Engineer; "DO" for District Office
(Engineering Division or other organization in the
District Office); "AO" for Area Office; "RO" for
Resident Office; and "PO" for Project Office. Codes
following the "G" typically are not used for Navy
projects.
Submittal items not designated with a "G" are
considered as being for information only for Army
projects and for Contractor Quality Control approval
for Navy projects.
**************************************************************************
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are [for Contractor Quality Control
approval.][for information only. When used, a designation following the
"G" designation identifies the office that will review the submittal for
the Government.] The following shall be submitted in accordance with
Section 01330 SUBMITTAL PROCEDURES:
SD-03 Product Data
Procedures and Methods
Personnel Qualification and Certification
Equipment Qualification Requirements
Copies of the procedure specifications. The procedure
qualification test records. The personnel qualification test
records.
SD-06 Test Reports
Reports and Results
Records of tests and inspections.
PART 2
PRODUCTS
2.1
ULTRASONIC EQUIPMENT
The ultrasonic test instrument shall conform to the requirements listed in
AWS D1.1/D1.1M, Section: Inspection, subsection, Ultrasonic Equipment,
except any requirement relating to weld inspection and the following
additional requirements:
2.1.1
Pulses
The ultrasonic test instrument shall be able to generate, receive, and
present pulses in any frequency in the 1- to 10-megahertz (MHz) range.
2.1.2
Horizontal Linearity Test
The horizontal linearity of the ultrasonic instrument shall be tested in
accordance with the requirements for horizontal linearity of paragraph
EQUIPMENT QUALIFICATION REQUIREMENTS, in addition to the AWS D1.1/D1.1M
SECTION 05092A
Page 12