VALVE MANHOLES AND ACCESSORIES
**************************************************************************
NOTE: Provide design details on drawings of
concrete reinforcing, size, dimensions of valve
manhole, piping arrangements, type of removable
cover, valve manhole penetrations, pipe and
equipment supports, etc.
**************************************************************************
3.5.1
Piping and Equipment in Valve Manholes
Piping and equipment in valve manholes shall be installed to provide easy
access without stepping on piping or equipment, and to provide sufficient
working room. Piping and equipment in valve manholes shall be installed
and supported as shown on the drawings. All globe, angle and gate valves
shall be installed with the stems horizontal or above. The Contractor
shall submit Data Package 2 as related to all equipment provided for the
project.
3.5.2
Sump Pumps Installation
**************************************************************************
NOTE: Coordinate this paragraph with the specified
requirements in paragraph SUMP PUMPS.
**************************************************************************
shall be hard wired.[ Monitoring of each pump motor and the high water
alarm shall be connected to the Energy Monitoring and Control System
(EMCS). Coordinate electrical requirements of EMCS with Section 16402
INTERIOR DISTRIBUTION SYSTEM]. Electrical circuits to the sump pumps shall
the "ON" position and will be signed as follows:
THIS CIRCUIT SUPPLIES POWER TO THE ELECTRIC SUMP PUMPS IN THE UNDERGROUND
DISTRIBUTION SYSTEM. THIS CIRCUIT MUST BE "ON" AT ALL TIMES; OTHERWISE
SECTION 02560