NOTE: Include the options "a" through "c" below for
LANTNAVFACENGCOM projects.
**************************************************************************
[a.
Sanitary piping installation parallel with water line:
at least 3 m 10 feet horizontally from a water line whenever
possible. The distance shall be measured edge-to-edge.
(2) Unusual conditions: When local conditions prevent a
horizontal separation of 3 m 10 feet, the sanitary piping or
manhole may be laid closer to a water line provided that:
(a) The top (crown) of the sanitary piping shall be at least 450
mm 18 inches below the bottom (invert) of the water main.
(b) Where this vertical separation cannot be obtained, the
sanitary piping shall be constructed of AWWA-approved ductile iron
water pipe pressure tested in place without leakage prior to
backfilling.
(c) The sewer manhole shall be of watertight construction and
tested in place.]
[b.
Installation of sanitary piping crossing a water line:
under water lines to provide a separation of at least 450 mm 18
inches between the top of the sanitary piping and the bottom of
the water line whenever possible.
(2) Unusual conditions: When local conditions prevent a vertical
separation described above, use the following construction:
(a) Sanitary piping passing over or under water lines shall be
constructed of AWWA-approved ductile iron water pipe, pressure
tested in place without leakage prior to backfilling.
(b) Sanitary piping passing over water lines shall, in addition,
be protected by providing:
1. A vertical separation of at least 450 mm 18 inches between the
bottom of the sanitary piping and the top of the water line.
2. Adequate structural support for the sanitary piping to prevent
excessive deflection of the joints and the settling on and
breaking of the water line.
3. That the length, minimum 6.1 m 20 feet, of the sanitary piping
be centered at the point of the crossing so that joints shall be
equidistant and as far as possible from the water line.]
[c.
Sanitary sewer manholes: No water piping shall pass through or
come in contact with any part of a sanitary sewer manhole.]
3.1.1.2
Earthwork
**************************************************************************
SECTION 02531
Page 29