2.3.8
Tilt Compensator
Provide tilt compensators as required.
2.4
Provide ground rods and connections in accordance with Section 16402,
"Interior Distribution System".
2.4.1
Grounding Block
Provide [corrosion-resistant] grounding block suitable for
[outdoor][indoor] installation.
2.5
BACKBOARDS
Provide void-free, fire rated interior grade plywood, 19 mm 3/4 inch thick,
[ 1200 by 2400 mm][ 4 by 8 feet][ as indicated]. Backboards shall be
painted with a gray, nonconductive fire-resistant overcoat. Do not cover
the fire stamp on the backboard.
PART 3
EXECUTION
3.1
INSTALLATION
3.1.1
Distribution System
**************************************************************************
NOTE: Show cable routing and equipment locations on
the drawings.
**************************************************************************
Distribution system shall conform to requirements specified herein.
Installation shall be in accordance with IEEE C2 and NFPA 70.
3.1.1.1
Raceway
**************************************************************************
NOTE: Use the bracketed option when conduit stubout
is provided for the local cable television company.
**************************************************************************
Provide cable installed in raceways such as conduit and cable trays in
compliance with NFPA 70. Raceway shall comply with Section 16402,
"Interior Distribution System." [Provide 78 mm 3 inch, minimum, PVC from
interior headend location to exterior CATV company connection location.
Coordinate location and requirements with the local cable television
company.]
3.1.1.2
Grounding System
**************************************************************************
NOTE: Show location of grounding blocks on
drawings. Grounding blocks may be used either
inside or outside. Since they are intended to
protect equipment from foreign currents, they are
most frequently placed inside, close to the cable
entrance.
**************************************************************************